Environmental equipment, instruments and meters, robots, ...

SF6Primary Function of Gas Leak Detection and Alarm System
Live DisplaySF6Gas Concentration
The system continuously collects and displays information from the monitored area within.SF6Gas Concentration.
Real-time updates on the operational control panel and backend monitoring computersSF6Concentration level.
Users can set alarm concentrations as needed.
Live Oxygen Concentration Display
In testingSF6The system also monitors oxygen content in addition to concentration.
Real-time oxygen concentration is displayed on the operation control panel and background monitoring computers.
The oxygen alarm concentration can be set according to user requirements.
Alarm Output
WhenSF6Should the oxygen concentration reach the preset alarm level, the operation control panel will emit audio-visual and voice alarms.
The system will notify the remote monitoring center through software agreements or hard-wired connections.
As per the settings, the system will automatically activate the fan for ventilation.

Infrared Sensing with Voice Alarms and Alerts
An infrared sensor is activated when someone approaches the switch room.
The operational control panel will emit voice prompts to notify staff of the current conditions inside the room.SF6Please ensure proper oxygen levels and suggest entering after the fan has been turned on for ventilation.
Fan Control
There are three ways to start the fan: timer, alarm, and forced.
Users can set4A scheduled start time and duration.
At the alarm concentration level, users can choose whether to automatically activate the fan.
The operational control panel features buttons to manually activate or deactivate the fans.
Humidity and Temperature Display
System displays temperature range:-40~60℃。
System displays humidity range:0~100.%RH。
Audio-Visual Alarm Control
Users can set the sound and light alarm to automatically turn off after a certain period of time after activation to minimize the impact on the surrounding area.
Detection Zone
System capable of multi-sensing24A regional solution, suitable for multiple switchgear rooms, helps to reduce users' investment costs.