Environmental equipment, instruments and meters, robots, ...

Please provide the Chinese content to be translated.Key Features
35kV,0.05Grade voltage transformers are high voltage grade, high accuracy voltage transformers that can be realized and verified.35kV, 0.1Transformer voltage ratios below a certain level, at a secondary voltage of100VPlease provide the Chinese content that needs to be translated.0.2VAThe secondary load.

II. Technical Indicators
1. Rated Voltage Ratio :35 kV /100V、35kV//100/V
2. Rated secondary capacity:0.2VA, 0.07VA, 0.02VA CosФ=1.0
3. Accuracy Level: 0.05No Chinese content provided. 、0.1 level, meaning under rated load conditions, when the voltage is within the range of 80% Un to 120% Un.Not greater than difference±0.02%, the angle difference is not greater than±0.6When the voltage is 50% Un, the difference is not greater than±0.03%, the error angle is not greater than±0.9At 20% of Un voltage, the difference is no greater than±0.04%, The angle difference is not greater than±1.2Actual error does not exceed the error limit.70%)
4. Test Voltage Once the winding withstands pressure1.2Un, 1 minute, double winding to ground, power frequency withstand voltage 2KV, 1 minute
5. Rated Frequency50Hz
www.114global.com © Zhongshang 114 Hebei Network Technology Co., Ltd.Address: Room 6009, Oriental New World Center, No.118 East Zhongshan Road, Qiaoxi District, Shijiazhuang City, Hebei ProvincePlatform Service Hotline: 4006299930