    Cable Insulation Resistance Standard

    2024-04-07

    What is the standard value for the insulation resistance of cables?


    If it's a 1KV cable, its insulation resistance value must not be less than 10 megohms.


    For cables rated 1-3KV, the insulation resistance must not be less than 200 megohms.


    For 6-10KV cables, the standard insulation resistance value should be greater than 400 megohms.


    For cables rated at 20-35KV, the standard for insulation resistance value required is not less than 600 megohms.


    For 220KV cables, the standard for insulation resistance is even higher, not less than 4,500 megohms.

    How to Measure Insulation Resistance


    Insulation resistance can be measured using an insulation resistance tester, a specialized device. It is crucial to switch off the main power supply before measurement. While doing so, discharge any ground shorts to prevent live measurements, as this can pose a safety hazard.


    Ensure the condition of existing high-voltage equipment is checked, and if any induction is detected, it must be eliminated before proceeding with the measurement. Clean the surface of the object to be measured thoroughly to avoid substances that may affect the resistance value, ensuring accuracy after measurement.


    Ensure the insulation resistance tester is in proper working condition. Pay close attention to the "0" and "∞" areas. Rotate the handle to reach the rated speed. If the pointer stops at the "0" area during a short circuit and at the "∞" area during an open circuit, it indicates normal operation.


    The insulation resistance tester must be placed on a flat surface without any rocking or movement, and there should be no significant external current conductors or magnetic fields nearby. Once everything meets the requirements, connect the lines for testing, and the displayed values are the insulation resistance readings.




Contact us

Wuhan E'dian Electric Power Test Equipment Co., Ltd.
Service Hotline 13808660749
Company Phone 400-034-8088
Company Address North of Guantan Second Road, Qiaokou District, Wuhan, Building 4, 1st Floor, Room 17 (HSBC Corporate Headquarters)

Message Consultation

 Click OK to indicate that you agree to《Service terms》《Privacy policy》

www.114global.com © Zhongshang 114 Hebei Network Technology Co., Ltd.Address: Room 6009, Oriental New World Center, No.118 East Zhongshan Road, Qiaoxi District, Shijiazhuang City, Hebei ProvincePlatform Service Hotline: 4006299930

 Click OK to indicate that you agree to《Service terms》《Privacy policy》