Dongguan Donghui Energy-saving Technology Co., Ltd., a professional electromagnetic heating equipment service provider, presents 15 practical operations for electromagnetic steam boilers today, to help you better utilize electromagnetic steam boilers.
Before equipment activation, ensure all valves and exterior positions are correct, and water and power supply are normal.
Prior to equipment use, water quality testing is conducted. Water quality is deemed acceptable if the hardness is ≤0.03 mmol/L; any hardness exceeding this standard is considered unacceptable. The frequency of water quality testing should be every two hours. Operations must be strictly adhered to the softened water procedure.
2. Turn on the power switch, the power indicator light illuminates, and activate the touch screen. Set the electromagnetic heater's switch to "on". The low water level alarm (due to insufficient water in the boiler) activates the pump to start running. Once the water level is replenished to the low level, the low water level alarm stops. The boiler operation indicator light turns on, the system automatically refills to the high water level, and the pump stops.
When the water level is low and the furnace pressure is low, the electromagnetic heater initiates heating automatically.
When the boiler pressure reaches the set value, the heating is automatically stopped. At this point, the steam valve can be opened to utilize the steam.
5. When using steam, the pressure inside the furnace decreases. Once it reaches the set lower pressure limit, the heating is initiated proactively.
When using steam, the water level in the boiler continuously drops. Once it reaches the low water level, activate the pump to replenish water in the boiler back to the high water level.
When the water level falls below the ultra-low level, the ultra-low water level alarm light illuminates and the boiler stops to replenish water until it exceeds the ultra-low level.
When the water level exceeds the high water level, the high water level alarm light illuminates and continues to heat until the water level falls below the high water level.
When the cylinder temperature reaches the set value (165℃), the corresponding electromagnetic heater stops heating until the cylinder temperature falls below the set value, at which point the electromagnetic heater activates automatically.
When the steam pressure reaches the set value of the pressure control switch (1.0 MPa), the electromagnetic heater stops heating and reports a steam pressure fault. The electromagnetic heater will activate again only when the steam pressure falls below the set value of the pressure control switch.
When the steam temperature reaches the set value (195℃), the electromagnetic heater stops heating and reports a steam temperature fault. It will only activate again once the steam temperature drops below 185℃.
12. Upon completion of the task, turn off the power by pressing the touch screen, extinguish the operational indicator light, and deactivate the electromagnetic heater switch.
At 0.15~0.1 MPa, flip the drain valve to discharge waste and close the inlet valve.
14. After boiler effluent has been successfully removed, close the effluent valve, open the filling valve, and shut the gas supply valve of the divider cylinder. Once the water supply is normal, close the filling valve. When the pressure in the divider cylinder reaches or exceeds 0.4 Mpa, slowly open 1/3 of the main gas supply outlet, then close it after one hour. Open 1/3 of the auxiliary pipeline gas supply outlet, and after the system heating is normal for one hour, fully open both the main and auxiliary gas supply outlets.
In the event of an emergency, the emergency stop switch should be engaged, followed by shutting down the main power supply.
Dongguan Donghui Energy-Saving Technology Co., Ltd. adheres to the operational philosophy of "people-oriented and customer-first," and is eager to cooperate and discuss business with all our new and existing clients. We strive to provide our clients with satisfactory, high-quality products and services, and we value their precious feedback.