Standard for Gas Pipeline Installation in Laboratory Cylinder Rooms
Pipelines for conveying dry gases should be installed horizontally. Pipelines for conveying wet gases should have a slope of no less than 0.3% and incline towards the condensate collector.
2. Oxygen pipelines and other gas pipelines can be mounted on the same framework, with a minimum spacing of 0.25 meters. The oxygen pipeline should be positioned above the other gas pipelines, which are not oxygen pipelines.
3. When laying pipelines parallel to combustible gas pipelines, the distance between them must not be less than 0.50 meters. When crossing, the spacing should not be less than 0.25 meters. In layered laying, the pipeline should be positioned above. Indoor pipelines should not be laid in ditches or directly buried. Avoid passing through unsuitable rooms.
4. Gas pipelines should not be installed on the same framework as cables and wiring laid on-site.
5. Seamless steel tubes should be used for gases. Pipes for gases with a purity of 99% or higher should be made of stainless steel, copper, or seamless steel tubes.
6. The connection part of pipelines and equipment should be made with metallic pipes. For non-metallic flexible hoses, polytetrafluoroethylene pipes and polyvinyl chloride pipes should replace rubber hoses.
Valves and accessories materials: Copper materials must not be used for gas pipelines. Other gas pipelines can be made from copper, carbon steel, malleable cast iron, and other materials.