详情描述

BWDK-3109B Dry-Type Transformer Controller

Hunan Changsha Liangwei Electrical Co., Ltd.

BWDK-3109B Dry Type Transformer Controller XMTB-3201A

BWDK-3109B Dry-Type Transformer Controller XMTB-3209

Key Technical Parameters

1. Terms of Use

Ambient Temperature: -10℃ to +55℃

Relative Humidity 5~95%

Atmospheric Pressure: 60~160 Kpa

Operating Voltage: AC170~AC250V (48~60Hz)

2. Measurement Range: -30.0~200℃

3. Resolution 0.1℃

4. Measurement Accuracy ±1℃

5. Control Accuracy ±1℃

6. Power Consumption < 8VA

7. Weight < 1 Kg

8. Sensor Parameters Pt100

9. Interference Resistance Meets JB/T7631 Standard

10. Contact Capacity

Fan: AC125/10A or AC220/7A, Set of 3 (optional)

Or single-phase active fan AC220/21A set

Over-temperature Alarm: AC125/10A or AC220/7A, set of one

Over-temperature trip: AC125/10A or AC220/7A, one set

11. Instrument exterior dimensions: 80×160×134mm

Embedded hole size: 152×76mm

BWDK-3109B temperature range settings are as shown in the table below:

Temperature T

  

Factory Set Temperature: °C

  

Adjustable temperature range: °C

  

Air Valve Closure Temperature T1

  

  80

  

  0-200

  

Fan startup temperature T2

  

  100(90)

  

  0-200

  

Over-temperature Alarm Temperature T3

  

  130(140)

  

  0-200

  

High-temperature Trip Temperature T4

  

  150

  

  0-200

  

Note: When setting, follow the order T4 > 13 > T2 > T1 + 4 (where 4 is the small return difference value for the fan's start-up and shutdown).