详情描述
1. Product Overview
Our modular air conditioning units are a type of air handling equipment developed by our company for direct temperature and humidity control of air. They feature innovative design, easy operation, stable operation, safety, reliability, and convenient maintenance. This series of units can meet various air volume requirements. Each standard model can be customized to fit customer needs with different functional sections, including initial efficiency fresh air section, surface condenser water section, heating section, humidification section, secondary return air section, fan section, noise reduction section, medium efficiency filter section, sterilization section, and heat recovery section. Different combinations of these functional sections can achieve various air treatment requirements.
Prior to shipment, the product has undergone pressure tests, vacuum tests, and operational tests. Simply install it, connect the necessary piping, and power it up to start using.
Design, manufacturing, and acceptance are all conducted in accordance with relevant specifications and standards.
This series of products can be custom designed and manufactured to meet specific customer requirements.

2. Product Features
Aesthetically pleasing
The panels are smooth with flat surfaces, the exterior panels are highly corrosion-resistant, and they can withstand UV rays, ensuring a clear and smooth appearance. The unit housing is equipped with a steel frame to ensure the overall strength of the unit, preventing deformation during transportation and use.
Good seal integrity
Special structure and sealed rubber of the unit, air leakage rate < 1%.
Eliminate cold bridges
Utilizing a unique anti-bridge frame, the double-layer panel features a high-pressure flame-retardant polyurethane insulation layer in between.
Advanced and unique, ensuring low-carbon environmental protection, comfortable and healthy.
The electrical control section utilizes PLC program control and a variable-frequency drive unit.
b. The air treatment section employs an air purification and sterilization system.
c. Noise management is achieved through a vibration and sound reduction system.

2. Product Features
Attractive appearance
Utilizing plain panels, the unit surface is smooth, the outer panels offer high-efficiency corrosion resistance, and can withstand ultraviolet radiation, with a clear and flowing appearance. The unit housing is lined with a steel frame, ensuring the overall strength of the unit, preventing deformation during transportation and use.
Good sealing properties
The unit features a special structure and sealed rubber, with an air leakage rate of <1%.
Eliminate cold bridges
Utilizing a unique cold-bridge-free frame, the double-layer panel features a high-pressure flame-retardant polyurethane insulation layer in between.
Advanced and unique, ensuring low-carbon and environmentally friendly, comfortable and healthy
The electrical control section is equipped with PLC program control and a variable frequency drive.
b. The air treatment section utilizes an air purification and sterilization system.
c. Noise management is achieved through a vibration-damping and sound-deadening system.
<
| Product Performance Parameters Table & Test Conditions | ||||||||||
| Combination Air Conditioner Dimension Reference Table (mm): 5-35 | ||||||||||
| Model: XL-ZKW | modle | 5 | 10 | 15 | 20 | 25 | 30 | 35 | ||
| Wide | wide | 1170 | 1500 | 1600 | 1800 | 2000 | 2250 | 2250 | ||
| High | height | 760 | 1050 | 1450 | 1600 | 1750 | 1900 | 2100 | ||
| LENGTH (sum of the lengths of the functional sections to be used) | ||||||||||
| Mixed Sections | Mixing section | 600 | 600 | 600 | 600 | 800 | 800 | 800 | ||
| Initial efficiency filter | early effect filter | 150 | 150 | 150 | 150 | 150 | 150 | 150 | ||
| Medium Efficiency Filter | medium efficiency filter | 600 | 600 | 600 | 600 | 600 | 600 | 600 | ||
| High-efficiency filtration section | high efficiency filters | 400 | 400 | 400 | 400 | 400 | 400 | 400 | ||
| Mid-section | Intermediate segment | 600 | 600 | 600 | 600 | 600 | 600 | 600 | ||
| Cooling Section (Four Rows) | Surface (4R)cooling section | 500 | 500 | 500 | 500 | 500 | 500 | 600 | ||
| Steam Heating Section | Steam heating section | 500 | 500 | 500 | 500 | 500 | 500 | 500 | ||
| Electric heating section | Electric heating section | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
| Dry steam humidification section | Dry steam humidification section | 500 | 500 | 500 | 500 | 500 | 600 | 600 | ||
| Moistened Film/Electrode Humidification Section | Electrode Humidifying Section | 500 | 500 | 500 | 500 | 500 | 600 | 600 | ||
| High-pressure micro-fog humidification section | High Pressure Microfog Humidification Section | 600 | 600 | 600 | 600 | 600 | 750 | 750 | ||
| Rotary Dehumidification Section | Runner dehumidification section | 1500 | 1800 | 1800 | 2000 | 2000 | 2000 | 2000 | ||
| Secondary air return section | Secondary return air section | 500 | 500 | 500 | 500 | 550 | 550 | 550 | ||
| Supply (Return) Fan Section | Fan section | 700 | 800 | 900 | 1000 | 1050 | 1150 | 1300 | ||
| Silencing Section | Muffler section | 1200 | 1200 | 1200 | 1200 | 1500 | 1500 | 1500 | ||
| Exhaust section | Outlet section | 600 | 600 | 600 | 600 | 800 | 800 | 800 | ||
| Combination Air Conditioner Dimension Reference Table (mm): 40-70 | ||||||||||
| Model: XL-ZKW | modle | 40 | 45 | 50 | 60 | 70 | 80 | 90 | ||
| Wide | wide | 2550 | 2550 | 2850 | 3350 | 4000 | 4000 | 4000 | ||
| High | height | 2100 | 2320 | 2320 | 2320 | 2320 | 2450 | 2550 | ||
| LENGTH (sum of the lengths of the functional sections to be used) | ||||||||||
| Mixed section | Mixing section | 800 | 1000 | 1000 | 1000 | 1000 | 1200 | 1200 | ||
| Initial efficiency filter | early effect filter | 150 | 150 | 150 | 150 | 150 | 150 | 150 | ||
| Medium-efficiency filter | medium efficiency filter | 600 | 600 | 600 | 600 | 600 | 600 | 600 | ||
| High-efficiency filter section | high efficiency filters | 400 | 400 | 400 | 400 | 400 | 400 | 400 | ||
| Middle section | Intermediate segment | 600 | 600 | 600 | 600 | 600 | 600 | 600 | ||
| Cooling plate section | Surface cooling section | 500 | 500 | 500 | 500 | 500 | 500 | 600 | ||
| Steam Heating Section | Steam heating section | 500 | 500 | 500 | 500 | 500 | 500 | 500 | ||
| Electric heating section | Electric heating section | 300 | 300 | 300 | 300 | 300 | 300 | 300 | ||
| Dry Steam Humidification Section | Dry steam humidification section | 600 | 600 | 700 | 700 | 700 | 700 | 700 | ||
| Wet Film/Electrode Humidification Section | Electrode Humidifying Section | 500 | 500 | 500 | 500 | 500 | 600 | 600 | ||
| High-pressure micro-fog humidification section | High Pressure Microfog Humidification Section | 600 | 600 | 600 | 600 | 600 | 750 | 750 | ||
| Tumble Dry Section | Runner dehumidification section | 2000 | 2200 | 2200 | 2500 | 2500 | 2500 | 2500 | ||
| Second air return section | Secondary return air section | 750 | 750 | 750 | 750 | 750 | 750 | 750 | ||
| Supply (Return) Fan Section | Fan section | 1300 | 1300 | 1300 | 1300 | 1300 | 1300 | 1300 | ||
| Silencing section | Muffler section | 1500 | 1500 | 1500 | 1500 | 1800 | 1800 | 1800 | ||
| Exhaust section | Outlet section | 800 | 800 | 1000 | 1000 | 1000 | 1000 | 1000 | ||
| Performance Parameters Table (5-17.5) | ||||||||||
| Project Model | Model: XL-ZKZ-S- | 5 | 7.5 | 10 | 12.5 | 15 | 17.5 | |||
| Nominal Airflow (m³/h) | Nomely air flow | 5000 | 7500 | 10000 | 12500 | 15000 | 17500 | |||
| Cooling Capacity (KW) | Refrigerating Mapacity | 27 | 37 | 54 | 66 | 79 | 92 | |||
| Heating Capacity (KW) | Heat production | 30 | 40.1 | 59 | 72 | 88 | 102 | |||
| External Back Pressure Range (PA) | External static pressure | 250-1200 | ||||||||
| Refrigerant Medium (Evaporator) | Cooling medium | 7℃ Frozen Water/R407a, R410a and other refrigerants | ||||||||
| Heating Medium (Condenser) | Heating medium | ≥ 45°C hot water or saturated steam of 0.3~0.4 Ma | ||||||||
| Condenser Material | Surface of cooler | Copper tube aluminum fin copper-aluminum expansion joints evaporative cooler | ||||||||
| Fan Type | Fan Type | Marine Centrifugal Fan | ||||||||
| Noise (dB) A | Noise | 68 | ||||||||
| Humidification Rate (KG/H) | humidifying capacity | 8 | 10 | 15 | 20 | 20 | 25 | |||
| Humidifier | humidifier type | Electrode Humidification / High-pressure Micro-fog Humidification / Infrared Humidification / Steam Humidification | ||||||||
| This product is a custom assembly; these are reference data. | ||||||||||
| Performance Parameters Table (20-32.5) | ||||||||||
| Project Model | Model: XL-ZKZ-S- | 20 | 22.5 | 25 | 27.5 | 30 | 32.5 | |||
| Nominal Airflow (m³/h) | Nomely air flow | 20000 | 22500 | 25000 | 27500 | 30000 | 32500 | |||
| Cooling Capacity (KW) | Refrigerating Mapacity | 106 | 119 | 132 | 145 | 158 | 171 | |||
| Heating Capacity (KW) | Heat production | 110 | 123 | 140 | 155 | 172 | 186 | |||
| Excess Pressure Range (PA) | External static pressure | 250-1200 | ||||||||
| Refrigerant (Evaporator) | Cooling medium | 7℃ Refrigerated Water/R407a, R410a and other refrigerants | ||||||||
| Heating Medium (Condenser) | Heating medium | ≥ 45°C hot water or 0.3~0.4 MPa saturated steam | ||||||||
| Cooling Table Material | Surface of cooler | Copper tube aluminum fin copper-aluminum expansion joints coil condenser | ||||||||
| Fan Type | Fan Type | Marine Centrifugal Fan | ||||||||
| Noise (db) A | Noise | 68 | ||||||||
| Humidification Rate (KG/H) | humidifying capacity | 25 | 25 | 30 | 35 | 40 | 45 | |||
| Humidifier | humidifier type | Electrode Humidification / High-Pressure Micro-Fog Humidification / Infrared Humidification / Steam Humidification | ||||||||
| This product is a customized assembly, and these figures are for reference only. | ||||||||||
| Performance Parameters Table (35-47.5) | ||||||||||
| Project Model | Model: XL-ZKZ-S- | 35 | 37.5 | 40 | 42.5 | 45 | 47.5 | |||
| Nominal Air Volume (m³/h) | Nomely air flow | 35000 | 37500 | 40000 | 42500 | 45000 | 47500 | |||
| Cooling Capacity (KW) | Refrigerating Mapacity | 184 | 197 | 210 | 223 | 236 | 249 | |||
| Heating Capacity (KW) | Heat production | 200 | 215 | 232 | 252 | 266 | 279 | |||
| Excess Pressure Range (PA) | External static pressure | 250-1200 | ||||||||
| Refrigerant Medium (Evaporator) | Cooling medium | 7℃ Refrigerated Water/R407a, R410a Refrigerants | ||||||||
| Heating Medium (Condenser) | Heating medium | ≥ 45°C hot water or 0.3~0.4 MPa saturated steam | ||||||||
| Condenser Material | Surface of cooler | Copper Tube Aluminum Fin Copper-Aluminum胀片 Plate and Frame Condenser | ||||||||
| Fan Type | Fan Type | Marine Centrifugal Fan | ||||||||
| Noise (db) A | Noise | 68 | ||||||||
| Humidification Rate (KG/H) | humidifying capacity | 45 | 45 | 45 | 45 | 45 | 45 | |||
| Humidifier | humidifier type | Electrode humidification/High-voltage micro-fog humidification/Infrared humidification/Vapor humidification | ||||||||
| This product is a custom assembly, and these figures are for reference only. | ||||||||||
| Performance Parameters Table (50-62.5) | ||||||||||
| Project Model | Model: XL-ZKZ-S- | 50 | 52.5 | 55 | 57.5 | 60 | 62.5 | |||
| Nominal Airflow (m³/h) | Nomely air flow | 50000 | 52500 | 55000 | 57500 | 60000 | 62500 | |||
| Cooling Capacity (KW) | Refrigerating Mapacity | 253 | 266 | 279 | 293 | 316 | 329 | |||
| Heating Capacity (KW) | Heat production | 280 | 290 | 306 | 313 | 334 | 366 | |||
| Excess Pressure Range (PA) | External static pressure | 250-1200 | ||||||||
| Refrigerant Medium (Evaporator) | Cooling medium | 7℃ Refrigerant Water, R407a, R410a, etc. | ||||||||
| Heating Medium (Condenser) | Heating medium | ≥ 45°C hot water or 0.3~0.4 MPa saturated steam | ||||||||
| Cooling Plate Material | Surface of cooler | Copper tube aluminum fin copper-aluminum expansion joint surface condenser | ||||||||
| Fan type | Fan Type | Marine Centrifugal Fan | ||||||||
| Noise (dB) A | Noise | 68 | ||||||||
| Humidification Rate (KG/H) | humidifying capacity | 45 | 45 | 45 | 45 | 45 | 45 | |||
| Humidifier | humidifier type | Electrode Humidification / High-pressure Micro-fog Humidification / Infrared Humidification / Steam Humidification | ||||||||
| This product is a custom assembly; these are reference data. | ||||||||||
| 2. Product Test Conditions Heating operating conditions: Air temperature -20°C, relative humidity 50%; air temperature 20°C, relative humidity 40%. Heating methods can be either hot water heating or steam heating. The performance parameters of the unit may change due to product improvements; no separate notice will be provided. Please refer to the product label for specific parameters. | ||||||||||
<
<
| Electrical and Automatic Control Systems | ||||||||||
| Xinglu modular air conditioning units can be configured with different types of control devices to meet user needs, enabling automatic control functions ranging from simple to complex. The standard configuration includes a switch-type start-up cabinet. ◆Container Launch The functional components of the modular air conditioning unit are controlled in a switch mode. For example: the start and stop of the fan motor, variable speed control of the fan motor, the start and stop of the electric heater, the on/off control of the electric valves in the chilled water, hot water, and steam pipelines, and the opening and closing of the air dampers; simultaneously, the unit is provided with various electrical protections and fault alarms, such as: overheat and overcurrent protection for the motor, protection against filter clogging, high-temperature alarm and control of the unit, etc. Smart Control System In addition to all the functions of the starting cabinet, it can directly monitor various internal parameters of the unit (such as temperature and humidity) and achieve constant temperature and humidity control. It also has stronger compatibility with other special components, allowing for automatic control of components like turntables, inverters, humidifiers, and heaters according to logical requirements. Additionally, it can be connected to the customer's BMS system to integrate the air conditioning system with other related systems, such as responding to fire alarms based on instructions from the customer's BMS system. | ||||||||||
| Safety Precautions | ||||||||||
| Upon arrival, if immediate unpacking and installation are not done, the product should be stored in a clean, well-ventilated indoor area. ◆The installation foundation should be elevated 100 ~ 200mm above the base level, with drainage ditches and ground drains set around the foundation. Ensure the foundation surface is level, with no more than a 0.7-degree slope along the length after the unit is installed, and no more than a 0.5-degree slope along the width. Adequate maintenance and operation space should be left around the unit. ◆The condensate drain pipe of the unit should be connected according to the diagram, ensuring that the water trap has sufficient height to facilitate the smooth drainage of condensate. | ||||||||||
询价单