Overview and Principle
This product is suitable for industrial, commercial, and civil infrastructure applications within buildings and similar premises, providing isolation protection for low-voltage distribution terminals at 50Hz AC, rated voltage of 380V, and rated current not exceeding 80A. It is also applicable for infrequent switching operations.
Applicable Working Environment and Installation Conditions
Ambient Temperature: -15°C to 40°C
Relative Air Humidity: ≤95% (No Condensation)
Altitude < 2000m
Pollution Level: 2
Areas with no significant vibration or shock
Product Features
Short Circuit Protection: The circuit breaker disconnects to protect against short circuits within 0.04 seconds.
C-type instantaneous trip current:

D-Type Instantaneous Breakaway Current:

Interrupting Current: lcs = lcn ≥ 6000A
Overcurrent (overload) protection:

Key Performance Indicators
Rated Voltage: AC 380V
Rated Line Current: 80A, 63A, 32A
Detent characteristics:
C-type instantaneous tripping current, 5-10In
D-type instantaneous trip current, 10-14In
Wiring capability
25mm² and below conductors
Meets Standards
GB/T 10963.1
Product Selection Sheet

Dimensions